Trane chiller password

$
0
0
Hi,

if anyone knows the password to chiller Trane Aquastream with tracer CH532,

please send to my email celektr@seznam.cz

user password 0000 is malfunction and another on forum too.

Thanks.Martin

Serious problem with Chiller Carrier 23XRV

$
0
0
Dear all,
- Fault state is 220: Ground Fault Trip; Check Motor and Current Sensors
- 2 minutes later, error appears 223 :Ground Fault Trip; Check Motor and Current Sensors
I checked GROUND FAULT CURRENT andVFD FAULT CODE in VFD_HIST screen , the fault code is 216.
When this error appear, I can't reset on ICVC display. I have to off power supply to Chiller, error reset
I measured grounded input wiring and insulation cable is OK
This is the 3rd time I encountered this error.
Can you give me any advice?
Best regards!
Thank you so much!

Mitsubishi VRF indoor units not cooling suffeciently

$
0
0
hi friends, i have installed Mitsubishi VRF but indoor units are not cooling sufficiently,
could any body help me to figure out the problem.on the remote controller there is no error shown, phase on the indoor is also ok.below are the model no of IDU and ODU.

Model no of ODU:PUHY-P450YHA(-BS)

Model no of IDU: PEFY-P250VMH-E x 2 Nos

container freezer

$
0
0
can anyone tell what is the suitable orifice size for a -20c maintaining 20ft container freezer..

carrier 30gx chiller EXV problem

$
0
0
Dear all.
we have a carrier 30gx chiller its expansion valve is not opening,we try through test its opening .but in normal condition its not working please help me to fix this

Necchi A 2290

$
0
0
Does anybody have technical knowledges from this old compressor, please?

Milk Pasteurizing Unit Visit

$
0
0
Dear Sir/Madam,

We have an investor who is trying to re-do their milk pasteurizing plant chilled water system with a new Mycom system.

Coming from an under developed region, we are more than willing to visit any world class milk pasteurizing unit over the world anywhere to pick up any best practices.

Is there anyone here who could manage such a visit and is also using Mycom on their facility?

It will help bringing safe clean milk and other by products in an under developed market!

Regards,

Prodialog carrier

$
0
0
Good day to all.
I need the software program to configure and control the control prodialog (30GX & HX). If anyone can help me.
Thanks in advance and good luck to all.
I leave my email piccauto@libero.it

Display Fridge Tripping HP Switch

$
0
0
Hi, I was asked to go and have a quick look at a beer display fridge yesterday evening, it is a J&E Hall condensing unit....unfortunately I don't have the model to hand. The data plate says R404a but at some point the compressor looks like it has been swapped out for a R134a compressor....which I know J&E Hall have units which you can choose which gas it runs so unsure if this is what the original compressor was or if the original was a r404a one. I checked to make sure the expansion valve was r134a and it is.

The paper work the last engineer left said he re-gassed the unit with R134a and put 4.3kg in, the sight glass is flashing through and for some reason it is tripping the HP switch even though it is set at 250psi. I couldn't tell you what the running pressures are on the high side as there is only one service point on the system and that is on the suction right before it goes into the compressor (not a rotor lock valve).

The discharge air from the condensing unit doesn't feel warm at all, the compressor seems to be running warmer than you would probably expect but not boiling....I suspected that there may be possibly air in the system and this is why the symptoms are like this? I have never come across this before so abit bemused by it...according to the guys paperwork all he has done is pressure test the system with nitrogen, repair a leak on a rotor lock valve on the receiver and re-gas!? I have also checked the condenser coil and it is clear, but I know from previous jobs even if it was blocked you would feel the excess heat and there doesn't seem to be much.

From what the customer told me the unit seemed to get down to temperature ok when it was first done but after a few days began not working. Anyone ever come across anything like this before...I have to go back Monday to try resolve the problem, so just wondering if I was going down the right track by reclaiming and recharging?

Thanks

Supermarket fridge - south

$
0
0
Hi All

who is doing supermarket fridge in the south, like kent / south east London area

any engineers on here in that area drop in :)

dew point temps

$
0
0
If I have R22 in a system and the suction pressure (psig) is 69 and the corresponding temperature is 40.30 and the superheat is 12.67, what would the dew point be?

:cool:

Wittemann Co2 compressor

$
0
0
Wittemann In Florida changed hands.
Anyone have a good contact, as want parts, no answers on website contact or by phone.
Any help appreciated

Daikin vrv drop in refrigerant

$
0
0
Hi all, I need to keep an old daikin 2 pipe r22 vrv system running for the summer its lost its charge would r417a be ok for this as a straight drop in, ie no oil change etc, once I've identified and repaired leaks, thanks in advance for any help.

York YAEP change parameter

$
0
0
Hi guys,

We have 3 nos. York YAEP (China) on site, recently one of them won’t loading more than 50%, further investigation found that discharge pressure unload change itself to 260 Psi while the other two still at 360 Psi. This parameter should be Factory Set. The program itself won’t allow us to set the parameter as YEAJ model.
Can we change this parameter on site? And how? or should we replace the eprom?
Need help/advise from experience guys especially on this YAEP unit, thanks in advance.

Control board (PCB) of aer onditioning fujitsu.

$
0
0
Hi!
I am intersting for control boar (PCB) of aer conditioning fujitsu AOY 60 TPA GT.This package is probably burned by lightning. I can read on PCB, EZ - 003 HHUE.
Whether it would be possible and a service manual, that it helps to make any possibility modification. Thank You

R22 to R422d oil change

$
0
0
Just wanted to see what other peoples opinions and ideas are on the subject of oil changes when converting from r22 to r422d. We have changed a few systems over now but there is still debate in our office as what to do in relation to changing the oil. Some people are saying change 5 to 10% to a Poe and some say Change the whole lot. Obviously just leaving the mineral oil is not the way to go but is there a reason as to why only changing a percentage of the oil rather than the full amount? Interested in anyone's response .
Thanks in advance

mcquay screw compressor

$
0
0
What is the power of the compressor SAL175QA13DA? How many horsepower?

CIAT LXH 1850Z-HPS, intermittent HP1 fault.

$
0
0
Scratching head.

getting hp fault on above 407c chiller, sometimes it will run for a day
(HP225 LP55 sup.h around 7k 3ish water TD).
Other times it will go in to fault before the contacts have even pulled in. To my knowledge I have checked all the components on the circuit that may throw up this fault, cant find any loose connections..

Has any body had this issue before, or can offer any advice. ANY welcome please.

please/thanks

Daikin FDQ250

$
0
0
Hello all. Today I had to commission a Daikin FDQ250 high velocity ducted unit. Prior to starting the unit I had concerns about the 230v power supply to the indoor unit, as this tapped off the 1, 2, 3 interconnecting cable to the L & N terminals (book says unit to have own 230v / 15amp supply), but Daikin tech confirmed that this isn't necessary and ok to tap off 1, 2, 3 from outdoor unit. Anyhow upon start checked the current draw of the indoor fan which was 8.5amp (data plate says 7.6mp), I was a little concerned as the power supply from outside is only a 6.3amp glass fuse off the outdoor board. After around an hour of operation and other checks, I walk back into the comms room to find a strong plasticky smell. I suspected the fan so check the amps which was now up to 10.5. Turned off the unit, remove the base panel to inspect the fan which extremely hot ( & the cause of the smell). The fan rotated freely with no resistance and there was no debris fouling the fan / impellers. I spoke to Daikin about the problem, checked winding resistance, connections etc, all ok. They asked about the ductwork design - there is none its just blows straight out of the spigots on the front down the room. They suggested that I should restrict the return air inlet, as there is no supply side duct to create air resistance. I duly blanked off 2/3 of the return air with some cardboard whilst monitoring the fan supply voltage and amperage. Immediately the fan amperage dropped from 10.5 to 4.5 amps, the voltage which was 225v increased to 230v. I settled on temporarily blanking 1/2 of the return air which saw the fan current settle at 6.5amp / 230v. Can anyone put some science to this? I was sceptical to their suggestion, but it worked, just want an explanation as to why.

Stonegate